An Offshore Flare System Facing Wind, Thermal and Nozzle Load Constraints
An offshore compressor station required a flexibility assessment of the piping running toward and from its flare seal drum (V-004). The work continued an earlier analysis of the same station’s flare system and covered the modified and continuation piping toward and from the drum.
The piping had a design pressure of 12 bar and a design temperature range of minus 20 to 95 degrees Celsius, with operating conditions of 9 bar and 95 degrees Celsius. The pipe material was A106B. The design temperature of the flare system headers had been reduced from 180 to 95 degrees Celsius. The location of the station required wind loads with a wind speed of 240 km/h to be included, using a uniform wind speed over the full height of the plant. Earthquake loads were not included.
The difficulty lay at the horizontal 16 inch inlet nozzle (N1). Thermal expansion of the longer pipe sections running perpendicular to N1 led to bending moments on the nozzle that exceeded the allowable. Modifications to the system were required to comply with the relevant codes and the client’s allowable nozzle loads.
CAESAR II Model, Code Checks and Load Cases
The piping was modelled and assessed in CAESAR II. The flare was added to the existing model from the earlier flare system analysis to create proper modelling conditions. The routing to the flare seal drum was updated from the latest isometrics, and the piping from the top of the drum was created as a separate model.
The flare seal drum was modelled as a large pipe so that the vertical thermal expansion of the vessel was included. Each nozzle was modelled as rigid from the vessel centreline to the vessel wall, to include the axial thermal expansion of the vessel, and as plain pipe with nozzle flexibility from the wall to the attached pipe, to represent the flexibility of the vessel wall. The vessel wall thickness was estimated from the thickness to diameter ratio of the attached pipe, with the remaining dimensions taken from the flare seal drum data sheet.
Piping stresses were assessed to ASME B31.3. Flanges were assessed with the equivalent pressure method: the forces and moments on the flange face are converted into an equivalent pressure, added to the design pressure and compared with the allowable flange pressure from the ASME B16.5 rating tables. With this method the system is downgraded and the design conditions are assessed only as an occasional load against the occasional allowable, while the operating conditions are used to check the flanges against the operating allowable. The forces and moments on N1 and on the vertical 24 inch outlet nozzle (N2) were checked in the axial, circumferential and longitudinal directions against the client’s allowable nozzle loads for each nozzle.
The load cases covered operating, sustained, occasional and expansion stress types. The operating cases included a cold case at minus 20 degrees Celsius. The occasional cases comprised the design conditions for the flange check and four wind cases, in which each of two wind loads was applied with positive and negative sign.
An Expansion Loop and Additional Supports for the Drum Piping
To bring the N1 loads within the allowable, it was recommended that the piping from the compressor station toward the flare seal drum be rerouted to create an expansion loop, with the addition of a rest support and an axial stop support. The client suggested the location and dimensions of the loop.
For the piping from the vertical N2 nozzle toward the flare tip, the support arrangement was determined on the assumption that the flare is unrestrained. The recommended arrangement for this line consists of three supports. All recommended supports were marked up on the isometrics.

Piping Stresses, Flange Loads and Nozzle Loads Within Allowables
With the recommended modifications, piping stresses were within the ASME B31.3 allowables in all reported load cases. The highest stress was 38.2 percent of the allowable, in the sustained case of weight and design pressure at node 14290. The highest occasional stress was 37.4 percent of the allowable, in a wind case at the same node, and the highest expansion stress was 15.5 percent of the allowable, at node 14038.
The first support after the drum, at node 14260, would lift off its rest support in the cold operating case at minus 20 degrees Celsius. No stresses above the sustained allowable were expected during this lift-off.
All flange loads were within the allowable values from the ASME B16.5 rating tables, and all nozzle loads were within the client’s allowable nozzle loads for N1 and N2. All components of the system therefore complied with ASME B31.3, the ASME B16.5 flange ratings and the client’s allowable nozzle loads.

Nozzle Loads and Support Lift-Off in Flare Seal Drum Piping
The N1 exceedance in this system came from thermal expansion of the longer pipe sections running perpendicular to the nozzle. With the expansion loop, the rest support and the axial stop support in place, the N1 loads were within the allowable values.
The operating cases covered both ends of the design temperature range, 95 and minus 20 degrees Celsius. The lift-off of the rest support at node 14260 was predicted in the cold case, and no stresses above the sustained allowable were expected during it. The nozzle loads were checked with the vertical thermal expansion of the drum, the axial thermal expansion of the vessel at each nozzle and the flexibility of the vessel wall all included in the model.

Frequently Asked Questions
How do you model a vessel nozzle in CAESAR II to include vessel thermal expansion?
In this project the flare seal drum was modelled as a large pipe so that its vertical thermal expansion was included. Each nozzle was modelled as rigid from the vessel centreline to the vessel wall, to include the axial thermal expansion of the vessel, and as plain pipe with nozzle flexibility from the wall to the attached pipe, to represent the flexibility of the vessel wall. The vessel wall thickness was estimated from the thickness to diameter ratio of the attached pipe.
How does the equivalent pressure method check flanges against ASME B16.5?
The forces and moments on the flange face are converted into an equivalent pressure, added to the design pressure and compared with the allowable flange pressure from the ASME B16.5 rating tables. With this method the system is downgraded: the design conditions are assessed only as an occasional load against the occasional allowable, and the operating conditions are checked against the operating allowable.
What caused the nozzle load exceedance at the flare seal drum inlet?
Thermal expansion of the longer pipe sections running perpendicular to the horizontal 16 inch inlet nozzle (N1) led to bending moments on the nozzle that exceeded the allowable.
Which modifications brought the flare seal drum piping within allowables?
For N1, it was recommended that the piping from the compressor station toward the drum be rerouted to create an expansion loop, with the addition of a rest support and an axial stop support. The client suggested the location and dimensions of the loop. For the line from the vertical N2 nozzle toward the flare tip, a recommended arrangement of three supports was determined on the assumption that the flare is unrestrained. With these modifications, all piping stresses, flange loads and nozzle loads were within their allowables.
What were the highest piping stresses in the ASME B31.3 assessment?
The highest stress was 38.2 percent of the allowable, in the sustained case of weight and design pressure at node 14290. The highest occasional stress was 37.4 percent of the allowable, in a wind case at the same node, and the highest expansion stress was 15.5 percent of the allowable, at node 14038.
Does support lift-off at minus 20 degrees Celsius overstress the flare seal drum piping?
Not in this system. The first support after the drum, at node 14260, would lift off its rest support in the cold operating case at minus 20 degrees Celsius, and no stresses above the sustained allowable were expected during this lift-off.