Flexibility Analysis of an Offshore Flare Header to ASME B31.3

ON THIS PAGE

Offshore Flare System Loads and Flange Overstress

An offshore compressor station system consists of five very similar compressor stations connected by one 42 inch header. The work covered the flare system of these compressor stations.

The location requires wind loads with wind speeds of 240 km/h to be included, with a uniform wind speed over the entire height of the plant. The design conditions are the same over most of the flare system but differ at the beginning of the header and at the scrubber vessel flare outlets of the compressor stations. The flare system headers have a design pressure of 12 bar and a design temperature of 180 °C, and the beginning of the header 15 bar and 80 °C. The outlets are designated V-X01 to V-X04, where V denotes the scrubber vessel, X applies to every compressor station and the last two digits identify the vessel. Their design pressures are 25, 40, 69 and 95 bar respectively, and their design temperature is 200 °C at V-X01 and 80 °C at the other three. The pipe material is A106B throughout.

The flexibility assessment of the flare system was performed to ASME B31.3 for the piping, with the flanges assessed against ASME B16.5 and, for the 42 inch flanges, ASME B16.47. In the original design, the design and operating temperature of the flare system caused multiple flanges to be overstressed. Rerouting of the system was not possible. The modifications made within the existing routing were a reduced design and operating temperature, flange repositioning where possible, and changes to restraint type and position.

CAESAR II Model and Load Cases for the Flare System

The flare system was modelled and assessed in CAESAR II to ASME B31.3. The model included the flare header with the PSV lines of the compressor stations.

Stress analysis model layout of the flare header with the PSV routing of the compressor stations.
Stress analysis model layout of the flare header with the PSV routing of the compressor stations.

Twelve load cases were defined: three operating (L1 to L3), two sustained (L4 and L5), five occasional (L6 to L10) and two expansion (L11 and L12). Wind loading based on a wind speed of 240 km/h was applied in four of the occasional load cases, L7 to L10. These combine W+P1, the loads of sustained load case L4, with two wind load cases, WIN1 and WIN2, each in positive and negative sense. Earthquake loads were not included.

The pipe was assessed in eleven of the twelve load cases. The flanges were assessed in two: operating load case L2, which also covers the pipe, and occasional load case L6.

Flange Assessment by the Equivalent Pressure Method

The flanges were assessed by the equivalent pressure method. The forces and moments acting on the flange face are converted to a pressure and added to the design pressure in the pipe. The resulting equivalent pressure is assessed against the allowable flange pressure from the ASME B16.5 rating tables, or ASME B16.47 for the 42 inch flanges. The equivalent pressure is Peq = 4F/(πG²) + 16M/(πG³) + Pdes, with units of N and mm. Here F is the force, M the moment, G the gasket diameter and Pdes the design pressure.

The second term, from the moment, has more influence than the first term, from the force, for gasket diameters smaller than 1000 mm, where the moment is induced by the force acting 1 m or more from the flange face. Where possible, the flanges were therefore repositioned to reduce the moment acting on the flange and with it the equivalent pressure at the flange face.

Design Condition Changes and Restraint Modifications

Two decisions were made in consultation with the client. The design and operating temperature used in the assessment were reduced to 95 °C; this was required to bring the flange loads within allowable values. The flange assessment was performed using operating conditions. This downgrades the system: the operating conditions are used to check the flanges against the operating allowable, and the design conditions are assessed only as an occasional load with the occasional allowable.

For the piping, the type and position of restraints were modified where necessary so that all stresses conform to the ASME B31.3 allowables. Support information and all modifications are shown on marked-up isometrics.

Flare System Stress, Flange and Nozzle Load Results

No modifications to the original routing were required. The modifications were the reduced design and operating temperature, flange repositioning where possible, and changes to restraint type and position. Results are recorded for the modified system only.

Load cases for the flare system, with the load combination, stress type and component assessed in each case.
Load cases for the flare system, with the load combination, stress type and component assessed in each case.

All piping stresses for the relevant load cases conformed to the ASME B31.3 allowables. All flanges in the inlet header were assessed, and all flange loads were within allowable values. The operating conditions were checked against the operating allowable and the design conditions against the occasional allowable. The flange assessment is included in the CAESAR II output. All nozzle loads on the equipment were within their allowable values.

The piping and flanges were analysed for the modified design and operating conditions, and with the recommended modifications all components of the system complied with the relevant code.

Transferable Practice for Fixed-Layout Flare Systems

Three points follow from this project for systems where the routing cannot change. First, flange overstress caused by the design and operating temperature was brought within allowable values without rerouting. The reduction of the design and operating temperature to 95 °C, made in consultation with the client, was required for this. The flanges were assessed against operating conditions, with the design conditions treated as an occasional load.

Second, the equivalent pressure relation shows where a flange remedy has effect. For gasket diameters smaller than 1000 mm, with the moment induced by a force acting 1 m or more from the flange face, the moment term has more influence than the force term. Repositioning a flange to reduce the moment at its face therefore reduces the equivalent pressure.

Third, the load case set separates the two flange checks. The flanges were assessed against the operating allowable in one operating load case, L2. The design conditions were checked against the occasional allowable in one occasional load case, L6.

Design pressure, design temperature, piping specification and pipe material for each section of the flare system.

Frequently Asked Questions

Which software and codes were used for the offshore flare header flexibility analysis?

The flare system was modelled and assessed in CAESAR II to ASME B31.3. The flanges were assessed against the ASME B16.5 rating tables, or ASME B16.47 for the 42 inch flanges.

Wind loading was based on a wind speed of 240 km/h, with a uniform wind speed over the entire height of the plant. It was applied in four occasional load cases, L7 to L10, which combine W+P1 with two wind load cases, WIN1 and WIN2, each in positive and negative sense. Earthquake loads were not included.

Twelve load cases were defined: three operating (L1 to L3), two sustained (L4 and L5), five occasional (L6 to L10) and two expansion (L11 and L12). The pipe was assessed in eleven of them and the flanges in two, operating load case L2 and occasional load case L6.

The forces and moments acting on the flange face are converted to a pressure and added to the design pressure in the pipe, using Peq = 4F/(πG²) + 16M/(πG³) + Pdes with units of N and mm. The resulting equivalent pressure is assessed against the allowable flange pressure from the ASME B16.5 rating tables, or ASME B16.47 for the 42 inch flanges.

For gasket diameters smaller than 1000 mm, where the moment is induced by the force acting 1 m or more from the flange face. Repositioning a flange to reduce the moment at its face therefore reduces the equivalent pressure.

In the original design, the design and operating temperature of the flare system caused multiple flanges to be overstressed. Rerouting of the system was not possible.

In consultation with the client, the design and operating temperature used in the assessment were reduced to 95 °C, which was required to bring the flange loads within allowable values, and the flange assessment was performed using operating conditions. Flanges were repositioned where possible, and the type and position of restraints were changed where necessary for the piping.

The operating conditions are used to check the flanges against the operating allowable, and the design conditions are assessed only as an occasional load with the occasional allowable.

Yes. All piping stresses for the relevant load cases conformed to the ASME B31.3 allowables, all flange loads in the inlet header were within allowable values, and all nozzle loads on the equipment were within their allowable values. With the recommended modifications, all components complied with the relevant code for the modified design and operating conditions, and no rerouting was required.