Water hammer on a sister platform and the GRE seawater system
The seawater system on a 690 MW offshore converter station provides seawater for cooling. During testing of the seawater system on a sister platform, water hammer effects were observed during an emergency shutdown of the seawater lift pumps, and water hammer loads and cavitation proved to be an issue there.
Because the piping on this platform closely resembles that of the sister platform, a pre-emptive simulation was performed to identify potential problems while the platform was still in the harbour. The connecting piping is Bondstrand 2000M glass-reinforced epoxy (GRE), with an axial tensile strength of 65 MPa and an axial elastic modulus of 10,000 MPa. The scope was a surge analysis and a static and dynamic stress analysis, with the surge model built from the seawater lift pump inlets to the overboard caisson nozzle.
Surge model in BOSfluids and stress model in CAESAR II
Seawater is lifted by four pumps submerged 11.3 m below grade and passes through two parallel filters and four parallel heat exchangers, at the elevation of the reactor deck 24.5 m above grade, to the overboard caisson. During normal operation, two pumps and one filter are in service. A three-dimensional piping model was built in CAESAR II from the project isometrics and P&IDs, then imported into BOSfluids, a one-dimensional single-phase transient flow solver, to simulate a series of upset scenarios.

Five upset scenarios were simulated: start-up of a first pump, start-up of a second pump while the first runs at nominal flow, a pump switch, and two pump-trip cases, pump trip 1 and pump trip 2, that differ only in which of the two filters is in service. In a pump trip, both active pumps shut down simultaneously while their motor-operated valves remain fully open. The pump trip proved the most critical scenario.
Two conservative assumptions were applied. As the isometrics refer only to Bondstrand 2000M, the epoxy was assumed to be IPD-cured rather than MDA-cured, which gives the lower allowables, and the pump valves were modelled as linear-opening valves.
Stresses and displacements were evaluated against ISO 14692-3. The long-term allowable stress envelope was constructed from the hoop and axial tensile strengths. As no manufacturer data was available, the qualified stress was taken as 0.85 times the hydrostatic design base of 148 MPa at 65 °C. This gives long-term allowables of 125.8 MPa for hoop stress (2:1) and 27.3 MPa for axial stress (1:0). Part factors of 0.67 for sustained, 0.83 for operational and 0.89 for occasional loads give allowables of 84.3, 104.4 and 112.0 MPa in hoop and 18.3, 22.6 and 24.3 MPa in axial stress. ISO 14692-3 also states a maximum deflection of 12.5 mm, against which the static displacements were checked.
Gravity-driven section and pump-trip unbalanced forces
A steady-state simulation was run first. At the nominal flow rate of 0.381 m³/s, the pressure at the vent, at the highest point of the system, was -0.03 barg for a fully filled pipe. Flow between the vent and the overboard caisson is therefore driven by the hydrostatic pressure difference over the elevation drop. As the actual pressure at the vent cannot fall below atmospheric (0 barg), air is drawn in. A steady-state analysis of this section gave a minimum flow rate of 0.389 m³/s to sustain pressure-driven flow, which implies that 2% of the volumetric flow there is air.
As the flow rate downstream of the vent is not sufficient to support the single-phase assumption of BOSfluids, the model was cut downstream of the vent and closed with an atmospheric boundary condition, which reproduces the flow behaviour upstream of the vent. For the section between the vent and the caisson, the maximum load was calculated by hand as the momentum of a fluid column that completely fills the pipe meeting an empty section at the maximum flow rate. The momentum force is F = ρV²A, with fluid density ρ = 1025 kg/m³, velocity V = 5.0 m/s and pipe cross-sectional area A = 0.077 m², giving 1973 N. This load may cause large deflections, because this section had only rest supports and no horizontal restraints. No unbalanced forces were available for this section, so no dynamic loads were applied to it in the stress model.
For pump trip 1, the scenario with the largest loads, the time histories of the unbalanced forces were exported from BOSfluids. They were applied in a linear time-history dynamic stress analysis in CAESAR II, after a static stress analysis of the same model with all equipment assumed anchored to the supporting structure.
In steady flow, the pressure thrust on two opposite elbows and the pipe wall friction are in equilibrium. While a pressure wave travels through the section between the elbows, they are no longer in equilibrium, and a net unbalanced force acts on the section. Half of each net force was applied at each end of its force-pair section. Four load cases were analysed: sustained (weight and pressure), operational (weight, pressure and temperature), dynamic (D1), and the combination D1+OPE, which was checked against the occasional allowable stress envelope.
Surge results for the five upset scenarios
None of the five upset scenarios showed severe water hammer effects or cavitation. In the pump start-up and pump switch scenarios, which are slower than a pump trip, the transient pressure effects were relatively small and no vacuum pressures, and hence no cavitation, were expected. The largest unbalanced forces in these scenarios, approximately 3000 N, occurred as the valves opened, in the pipe section behind the valves and in the pumps outlet header.
During the pump trip, the flow rate in the pumps outlet header fell to zero in 3 seconds. The two pump-trip cases differed only slightly, with pump trip 1 showing slightly higher pressure peaks and unbalanced loads. The minimum pressure was -0.35 barg at the filters inlet header, well above the vapour pressure of 0.03 bara, so no cavitation was expected. The largest unbalanced force in any scenario, approximately 4400 N, occurred in pump trip 1 at the moment the pumps tripped. It acted on the pipe section between the pumps outlet header and the filters inlet header.
The seawater systems on the two platforms differ in two main respects. The sister platform contained an additional minimum-flow check valve, which appears to have contributed to its water hammer event; this platform has no such valve. On this platform, the filters, the heat exchangers and especially the pump discharge sit a couple of metres below the highest point of the system, where the atmospheric air vent connects. The resulting increase in hydrostatic pressure at the pump discharge, relative to the sister platform, is enough to prevent cavitation and gives a margin for pressure fluctuations at the equipment.
In combination with the structural natural frequencies of the system, the unbalanced forces from the upset scenarios may cause high stresses in the piping, and the dynamic stress analysis was performed to assess this.
ISO 14692-3 stress, displacement and restraints
In the original layout, the highest static stress was 89% of the sustained allowable, at the loop before the heat exchanger inlet header, with a displacement of 36.0 mm at the same location. At the unsupported bend between the vent and the caisson, the stress was 71% of the sustained allowable and the displacement 15.5 mm. The static stresses were within the ISO 14692-3 allowables, but both displacements exceeded the 12.5 mm maximum deflection. The highest dynamic stress, for D1+OPE, was 75% of allowable and within the occasional allowable envelope. The dynamic displacements, up to 31.6 mm at the heat exchanger inlet header, were considered large.
Additional rest supports were specified to reduce the static displacements in the vertical direction. Additional restraints, which can be placed at existing rest support locations, were specified to reduce the dynamic displacements in the horizontal direction. The new restraints are guides, axial stops and a 3-way stop, and include restraints on the line from the vent to the caisson, which previously had rest supports only. The restraints were marked up on the project isometrics.
With the modified support arrangement, the highest static stress fell to 61% of allowable and the largest static displacement to 9.5 mm, below the 12.5 mm maximum deflection. The highest dynamic stress fell to 60% of allowable and the largest dynamic displacement to 17.5 mm. The largest horizontal support loads are in the new axial stops in the heat exchanger inlet header: 2.9 kN static and 8.3 kN dynamic.
| Original layout | Modified layout | |
|---|---|---|
| Highest static stress (% of allowable) | 89% | 61% |
| Largest static displacement | 36.0 mm | 9.5 mm |
| Highest dynamic stress (% of allowable) | 75% | 60% |
| Largest dynamic displacement | 31.6 mm | 17.5 mm |
| Largest horizontal support load, static | 2.6 kN | 2.9 kN |
| Largest horizontal support load, dynamic | 2.9 kN | 8.3 kN |

Sister platform comparison and GRE support design
Although the two platforms have closely similar piping, the surge results differed. Water hammer loads and cavitation proved to be an issue on the sister platform. On this platform, which has no minimum-flow check valve and has its equipment a couple of metres below the vent, no upset scenario produced severe water hammer or cavitation.

For the GRE piping in this system, the original layout was within the ISO 14692-3 stress allowables, and the additional supports and restraints were required to reduce the static and dynamic displacements. The analysis identified this while the platform was still in the harbour.
Frequently Asked Questions
Why was a surge analysis carried out on this offshore seawater cooling system?
During testing on a sister platform, water hammer effects were observed during an emergency shutdown of the seawater lift pumps, and water hammer loads and cavitation proved to be an issue there. The piping on this platform closely resembles that of the sister platform. A pre-emptive surge analysis and a static and dynamic stress analysis were therefore performed while the platform was still in the harbour.
Did a pump trip cause water hammer or cavitation in the GRE seawater system?
No. None of the five upset scenarios showed severe water hammer effects or cavitation. The pump trip was the most critical scenario. Its minimum pressure was -0.35 barg at the filters inlet header, well above the vapour pressure of 0.03 bara. The largest unbalanced force was approximately 4400 N, in pump trip 1.
Why did this seawater system behave differently from its sister platform?
The two systems differ in two main respects. The sister platform had an additional minimum-flow check valve, which appears to have contributed to its water hammer event. On this platform, the filters, heat exchangers and pump discharge sit a couple of metres below the vent at the highest point of the system. This increases the hydrostatic pressure at the pump discharge enough to prevent cavitation.
How was the gravity-driven section downstream of the vent handled in a single-phase surge model?
The steady-state model gave -0.03 barg at the vent. The actual pressure cannot fall below atmospheric, so air is drawn in, about 2% of the volumetric flow. As this flow does not support the single-phase assumption of BOSfluids, the model was cut downstream of the vent and closed with an atmospheric boundary condition. The maximum load in the section between the vent and the caisson was calculated by hand as a fluid-column momentum force of 1973 N.
How are BOSfluids unbalanced forces applied in a CAESAR II time-history analysis?
For pump trip 1, BOSfluids calculates the net unbalanced force on each elbow-pair section from the time-dependent pressure difference. These force time histories are exported to CAESAR II. Half of each net force is applied at each end of its section in a linear time-history analysis. The combined case D1+OPE is then checked against the ISO 14692-3 occasional allowable stress envelope.
What maximum deflection does ISO 14692-3 state for GRE piping, and how did this system compare?
ISO 14692-3 states a maximum deflection of 12.5 mm. In the original layout, the static displacement was 36.0 mm at the loop before the heat exchanger inlet header and 15.5 mm at an unsupported bend, although the highest static stress was 89% of the sustained allowable. With the modified support arrangement, the largest static displacement fell to 9.5 mm.
Which supports were added to reduce the GRE piping displacements?
Additional rest supports reduce the vertical static displacements. Guides, axial stops and a 3-way stop reduce the horizontal dynamic displacements, including restraints on the line from the vent to the caisson. The new axial stops in the heat exchanger inlet header carry the largest horizontal support loads: 2.9 kN static and 8.3 kN dynamic.