Transient Surge Analysis of a 1200 mm GRE Seawater System for Two Vaporisers

ON THIS PAGE

Vacuum Risk in a Buried 1200 mm GRE Seawater Supply

The seawater system supplies two vaporisers from a pump manifold through two buried glass-reinforced epoxy (GRE) lines of 1200 mm diameter. Three pumps are connected to the manifold, one of them on standby, each with a capacity of 5,500 m³/h. Five pumps (one on standby) and four vaporisers might be connected in future, and the upset conditions considered both two pumps active and four pumps active. Each pump can run at two speeds: 992 RPM, which delivers 5,500 m³/h, or 744 RPM, which delivers 2,750 m³/h.

The piping is reinforced fibreglass, a Class A system according to the Service Limit State (SLS), with a design pressure of 8 barg. The system initially had no vacuum breakers. Emphasis was placed on whether vacuum could arise in any upset scenario, and on whether vacuum breakers needed to be installed.

CAESAR II Pipe Model Exported to BOSfluids

Surge was assessed according to ISO 14692, the applicable standard for fibreglass piping systems. The piping was first modelled in the pipe stress program CAESAR II from the project isometrics. That model was exported to BOSfluids, where the pumps, valves and other boundary conditions were added before the model was analysed for each upset scenario. Two later changes had no significant influence on surge: a revised routing near the pump house, and a 15 m relocation of the seawater intake that added a bend in the buried lines. The model was therefore taken as an accurate representation of the as-built system.

The inputs were the pump curves, the piping model and the pumps. Flows and pressures throughout the system were results of the simulation. In each scenario the pumps were started and then stopped as the scenario defined, and BOSfluids calculated the response of the fluid.

The design data were those of the project’s GRE pipe. Structural wall thicknesses conformed to EST 8 (8 barg design pressure), from 2.8 mm at ND 350 to 9.7 mm at ND 1200. The material was modelled with an axial elastic modulus of 12,000 MPa, a circumferential elastic modulus of 20,500 MPa, a shear modulus of 11,500 MPa and Poisson ratios of 0.38 (hoop/tensile) and 0.65 (axial/hoop). The pipe content was water with a density of approximately 1,050 kg/m³.

Pump-Trip Scenarios Selected by Surge Severity

Five upset scenarios were analysed in BOSfluids. They were chosen as the worst scenarios for the system in surge terms, which are not necessarily the most likely.

The model had four pumps, P751A to P751D, connected to the manifold. The first two scenarios were a complete power failure with four pumps running and stopping simultaneously, at 744 RPM and at 992 RPM respectively. In both, the pumps ran down gradually on the inertia of pump and driver. The remaining three scenarios stopped a single pump, P751A, in two seconds due to a mechanical problem. Scenario three placed that stop against three other pumps still running at 744 RPM. In scenarios four and five, P751A was running alone, at 744 RPM and at 992 RPM respectively. Scenario four is unlikely, but in surge terms it is more extreme than scenario three.

Each scenario was solved for steady state and transient conditions. The steady-state solution gave the pressure, flow rate and velocity distributions. The transient solution recorded the maximum and minimum pressure reached at every node, so each plotted distribution combines values from different time frames. Time histories of the pump trip were plotted at seven nodes: two in the pump manifold, one in the middle of each 1200 mm header, one in the vaporiser manifold and one in the middle of each branch connection to the two vaporisers.

Two further scenarios were considered and not analysed in detail. Two pumps running with one stopping in two seconds was judged less extreme than scenarios four and five, because the remaining running pump reduces the chance of vacuum. Four pumps all stopping in two seconds on mechanical failure was excluded because simultaneous mechanical failure of all four pumps is highly unlikely.

3-D model of a buried 1200 mm GRE seawater system showing steady-state pressure in barg with four pumps running at 992 RPM.
Steady-state pressure distribution in barg with four pumps running at 992 RPM, from the pump manifold through both 1200 mm GRE lines to the vaporiser manifold.

Minimum and Maximum Pressures by Pump-Trip Scenario

In scenario one, the four-pump power failure at 744 RPM, the maximum pressure was 3.2 barg, well within the allowable of the system. In scenario two, the same power failure at 992 RPM, the lowest pressure was -0.18 barg, well within the vacuum capability of the GRE pipe.

In scenario three, the three pumps still running at 744 RPM outweighed the effect of the two-second stop of P751A. In scenarios four and five, with P751A running alone, full vacuum did not occur anywhere in the system. With one pump running, flow rates and velocities were low.

The highest pressure across the five scenarios was 5.6 barg, in scenario five, well below the maximum allowable of 10.6 barg for the EST 8 system (8 barg design pressure x 1.33).

3-D model of a 1200 mm GRE seawater system showing minimum transient pressure after a four-pump power-failure trip from 992 RPM, lowest value -0.18 barg.
Minimum pressure in barg reached at each node after four pumps running at 992 RPM trip on power failure. The lowest value is -0.18 barg, and the values at different nodes occur at different times.

No Vacuum Breakers, Air Release Valves at High Points

The system was concluded to be fit for purpose, with no need to install vacuum breakers. On a power failure, the predicted spin-down time of the pumps is long enough to prevent full vacuum. A stop in two seconds is only possible with a mechanical problem, such as a bearing problem. It would only be the decisive case for vacuum if more than one pump stopped this way, and that combination was treated as double jeopardy and not taken into account.

A few air release valves are required at local high points to vent entrapped air.

Selecting scenarios by surge severity brought an unlikely single-pump stop into the assessment alongside the power-failure cases. The vacuum breaker question was settled by simulating the system as designed, with none fitted, and comparing the results with full vacuum and with the vacuum capability of the GRE pipe.

Plot of pump speed in RPM over 90 seconds as one pump runs down after a four-pump power-failure trip from 992 RPM.
Run-down of one pump over 90 seconds after four pumps running at 992 RPM trip on power failure.

Frequently Asked Questions

Did the buried GRE seawater lines need vacuum breakers?

No. Five pump-trip scenarios were simulated in BOSfluids on a system initially built without vacuum breakers, and the system was concluded to be fit for purpose with no need to install them. In the four-pump power failure at 992 RPM, the lowest pressure was -0.18 barg, well within the vacuum capability of the GRE pipe. A few air release valves are still required at local high points to vent entrapped air.

When all four pumps lose power, they run down gradually on the inertia of pump and driver. The predicted spin-down time is long enough to prevent full vacuum, which is why the power-failure cases did not call for vacuum breakers.

Full vacuum did not occur in either single-pump case, with P751A running alone at 744 RPM or at 992 RPM before a two-second stop. With one pump running, flow rates and velocities were low. When three other pumps were still running, they outweighed the effect of the stop. A stop in two seconds is only possible with a mechanical problem, such as a bearing problem. It would only be the decisive case for vacuum if more than one pump stopped this way, which was treated as double jeopardy.

They were selected as the worst cases in surge terms, which are not necessarily the most likely. The five scenarios analysed were:

  • four pumps tripping on power failure at 744 RPM
  • four pumps tripping on power failure at 992 RPM
  • one of four running pumps stopped in two seconds
  • one pump running alone stopped in two seconds, at 744 RPM
  • one pump running alone stopped in two seconds, at 992 RPM

Two pumps running with one stopping was judged less extreme than the single-pump cases. Four pumps all stopping in two seconds was excluded as highly unlikely.

The maximum allowable was 10.6 barg, taken as the 8 barg design pressure multiplied by 1.33. The highest pressure across the five scenarios was 5.6 barg, in the case of one pump running alone at 992 RPM.

The piping was modelled in CAESAR II from the project isometrics and exported to BOSfluids. The pumps, valves and other boundary conditions were then added there. The pump curves, the piping model and the pumps were the inputs, and flows and pressures were results of the simulation.