Pipework Displacement During a Seawater Lift Pump ESD
During commissioning of the seawater cooling system at an offshore HVDC substation, an emergency shutdown (ESD) of the seawater lift pump produced uncontrolled displacement of the connected 12-inch glass-reinforced epoxy (GRE) pipework. Video of the test showed an estimated 18 mm of axial displacement at support PS-0482. Photographs showed an estimated 15 mm of lateral displacement at guide support PS-149. At the ESD, the line at PS-0482 first moved a small amount downstream. Around 1.2 seconds later it moved upstream and then recoiled downstream, accompanied by a loud bang. The clamped guide at PS-149 was reported to have moved.
The loads behind the movement were unknown. The analysis set out to determine the loads on the system following the ESD and their effect on pipe stresses and support loads. It also set out to identify the mechanism that produced them and to propose modifications.
Surge Analysis of the Pump ESD in BOSfluids
During steady flow, the pressure thrust on a pair of opposite elbows is balanced by the wall friction in the pipe section between them. A transient upset, such as a valve closure or a cavity collapse, sends pressure waves through the system. While a wave passes between the elbows, the balance is lost and a net unbalanced force acts on the pipe section, directed towards the high-pressure side.
To quantify these forces, the piping was modelled in BOSfluids, starting from the existing CAESAR II piping model. A steady state defining the flow rate and pressure distribution was solved first and used as the starting point for the pump ESD transient. The steady state was based on equipment pressure drops, pump curves and pump settings supplied by the client; the exact steady-state conditions were not available.

Three candidate mechanisms were identified for the observed loads. The first was the discharge pressure drop at pump shutdown. The second was cavitation and column separation. Rapid deceleration of the water column can cause pressure in the upper pipe sections, where hydrostatic pressure is lowest, to drop below vapour pressure, and the vapour cavities may produce high pressure spikes and large unbalanced loads when they collapse. The third was backflow through the minimum flow check valve, located in the riser downstream of the pump, if it did not close fast enough. This was considered unlikely because the valve contains a spring that should be capable of closing it before backflow occurs.
Two transient cases were run to reconstruct the observations and were expected to cover the range of possible minimum flow check valve behaviours. The pump tripped at 1.0 s in both cases. In Case 1 the valve closed between 1.4 s and 2.0 s, starting when the pressure drop across it fell below 0.1 barg. In Case 2 the valve closed rapidly between 2.4 s and 2.45 s, on the assumption of significant backflow through the valve at that time. This case set aside the expected valve behaviour and was based on the video observations.
Dynamic Time-History Stress Analysis in CAESAR II
The unbalanced force time histories from Case 1 were applied to a dynamic time-history stress analysis in CAESAR II. The load profiles of the two cases are similar, so the stress results for Case 2 would be similar as well. The material properties in the original model did not conform to the data sheet for the piping, so they were corrected to the values for Bondstrand 2000M. Stresses were assessed against the allowable limits of the 1994 UKOOA specification.
Four models were analysed: the original model (Model 1); Model 1 without the PS-149 guide (Model 2); Model 1 with additional flexibility to model the piping towards the pump (Model 3); and Model 3 without the guide (Model 4). The guide was removed in Models 2 and 4 to obtain the maximum displacement possible under the applied loads.
The calculated displacements were compared with those observed during the ESD. At PS-149, the two models without the guide gave 18.9 mm (Model 2) and 17.7 mm (Model 4) against the estimated 15 mm. At PS-0482, Model 3 gave 18 mm against the estimated 18 mm, while Models 1, 2 and 4 gave 10.4, 11.1 and 24.8 mm respectively. The observations can therefore be matched with a reasonable degree of accuracy by the surge analysis and the CAESAR II dynamic stress analysis.
| Location | Model 1 | Model 2 | Model 3 | Model 4 | Observed (estimated) |
|---|---|---|---|---|---|
| PS-149 lateral | not reported | 18.9 mm | not reported | 17.7 mm | 15 mm |
| PS-0482 axial | 10.4 mm | 11.1 mm | 18 mm | 24.8 mm | 18 mm |
Cavity Collapse, Guide Load, Maximum Pressure and UKOOA Stress
The analysis identified collapse of a cavity forming downstream of the minimum flow check valve as the most likely cause of the waterhammer. In both cases the pump ESD produced an unbalanced force of 7.0 kN on the line at 1.08 s. In Case 1, cavity collapse at 4.02 s produced 16 kN in the opposite direction. In Case 2, closure of the minimum flow check valve at 2.46 s produced an unbalanced force in the order of 16 kN, and cavity collapse at 4.6 s produced 20 kN. It is uncertain whether this predicted collapse occurred in reality.
In Case 1 the larger force occurred later than the 1.2 s interval observed. In Case 2 the timing of both the initial force and the second force, from minimum flow check valve closure, agreed with the observations.

With the Case 1 loads, the lateral load on PS-149 was 6.0 kN in Model 1 and 6.5 kN in Model 3. The maximum allowable static lateral load for the MIC-SPH-90 guide type is 5 kN. The guide provides lateral restraint through friction between bolted clamps and the supporting steel beam. Under a dynamic load of this magnitude, it is highly likely that the friction force mobilises too slowly to prevent displacement of the clamps. Friction-based restraints have limited functionality under dynamic load conditions, and the dynamic and sudden nature of the load may have caused the guide function to fail.
Maximum pressure, at the pump discharge flange, was 9.87 barg in Case 1 and 9.9 barg in Case 2. Neither case predicted pressures exceeding the design pressure of the line. The highest calculated axial stress was 17.7 MPa at node 2108, the 45-degree bend between the pump and the manifold, in Model 3.
The UKOOA long-term allowable axial stress without hoop stress applies because pressure is low during the ESD; its value is 18.3 MPa. It is derived from the Bondstrand 2000M data sheet characteristic values for an assumed IPD-cured system: 300 MPa in the hoop direction at the 2:1 hoop-to-axial stress ratio, 65 MPa in the axial direction at the 0:1 ratio, and a hydrostatic design base (HDB) of 148 MPa. The derivation applies the UKOOA default ratio f1 of 0.85 between the lower confidence limit (LCL) and the HDB, and the load-case-dependent system design factor f2. On this basis the dynamic stresses during the ESD are acceptable.
Mitigation by Axial Stop, Welded Guide or Air Valve
Three possible options were proposed to reduce the observed displacements and stresses. An axial stop at PS-0482, in the horizontal run downstream of the pump, was analysed dynamically with the surge loads. With the PS-149 guide retained, the lateral load on PS-149 fell to 3.7 kN. With the guide removed, the displacement at PS-149 was 6 mm.

In the second option, the clamped guide at PS-149 may be replaced by a welded connection able to withstand the calculated forces. This could be either a structure supporting the pipe shoe or a T-bar welded to the supporting structure. It changes the physical implementation of the support but not the flexibility model, and the maximum stresses remain below the UKOOA allowable.
The third option addresses the mechanism. An additional air valve downstream of the minimum flow check valve, at the highest pipe section, is a possible resolution. It would prevent the low pressure responsible for the cavity collapse and the high unbalanced loads. Additional analyses would be required to size the air valve and determine its optimum placement.
Frequently Asked Questions
What caused the waterhammer after the seawater lift pump ESD?
The analysis identified collapse of a cavity forming downstream of the minimum flow check valve as the most likely cause. After the pump trip, pressure in the upper pipe sections can drop below vapour pressure. When the cavity collapsed in Case 1, it produced an unbalanced force of 16 kN on the line.
Why did the friction-clamped pipe guide move during the pump ESD?
With the Case 1 loads, the lateral load on the guide was 6.0 kN in Model 1 and 6.5 kN in Model 3. The maximum allowable static lateral load for the MIC-SPH-90 guide type is 5 kN. The guide restrains the pipe laterally through friction between bolted clamps and a steel beam. Under a sudden dynamic load, it is highly likely that the friction force mobilises too slowly to prevent the clamps displacing.
Were the GRE pipe stresses within the UKOOA allowable during the ESD?
Yes. The highest calculated axial stress was 17.7 MPa at a 45-degree bend between the pump and the manifold. The UKOOA long-term allowable axial stress without hoop stress is 18.3 MPa, so the dynamic stresses are acceptable. Maximum pressure was 9.87 barg in Case 1 and 9.9 barg in Case 2, and neither case exceeded the design pressure of the line.
How is the UKOOA allowable axial stress for GRE pipe derived when hoop stress is low?
The derivation starts from the Bondstrand 2000M characteristic values for an assumed IPD-cured system: 300 MPa hoop at the 2:1 stress ratio, 65 MPa axial at the 0:1 ratio, and a hydrostatic design base of 148 MPa. It then applies the UKOOA default LCL-to-HDB ratio f1 of 0.85 and the load-case-dependent system design factor f2. For this system the result is 18.3 MPa.
How was the transient model checked against the field observations?
Calculated displacements from four CAESAR II models were compared with those estimated from video and photographs of the ESD. At the guide, the models without the guide gave 18.9 mm and 17.7 mm against an estimated 15 mm. At PS-0482, one model gave 18 mm against an estimated 18 mm. The observations can be matched with a reasonable degree of accuracy.
What options were proposed to reduce the pipe movement?
Three options were proposed:
- An axial stop downstream of the pump. With the guide retained, it reduced the guide load to 3.7 kN; with the guide removed, it limited the guide displacement to 6 mm.
- Replacing the clamped guide with a welded connection.
- An additional air valve downstream of the minimum flow check valve, which would prevent the low pressure that drives the cavity collapse. Sizing and placing the air valve would require additional analyses.