Bellow Overextension in a DN800 GRE Seawater Spool
A DN800 spool in glass-fibre reinforced epoxy (GRE) was to be installed to transport seawater. The GRE material has unequal axial and hoop stiffness, with an axial elastic modulus of 10,500 MPa and a hoop elastic modulus of 20,500 MPa. Its “effective” Poisson ratio is 0.38. The original layout placed a 300 mm bellow near the caisson connection.
The bellow is untied. It was modelled without tie-rods, and the pressure thrust is assumed to be accommodated by the end connections. Because of the untied bellow, internal pressure causes no axial stress in the spool. It does cause a positive hoop strain in the GRE pipe. Through the Poisson effect, this produces an axial contraction of the pipe and, with it, an axial extension of the bellow.
At the 10 barg design pressure, the total axial contraction of the GRE pipe was approximately 16.4 mm. With the bellow installed in the normal way, the modelled axial bellow extension was 18.7 mm against a maximum allowable extension of 10 mm. The spool had already been produced, so a solution had to be found for the spool as produced.
CAESAR II Static Stress Model and ISO 14692 Assessment
The system was analysed with a static stress model in CAESAR II to verify the stress levels and bellow displacements against their allowable values. The GRE piping was assessed against ISO 14692. The allowable stress envelope was drawn up from the GRE strength values: short-term biaxial hoop strength 250 MPa, short-term uniaxial strength 65 MPa, qualified strength 125 MPa and long-term uniaxial strength 32.5 MPa.
The model included the connected steel piping for overlap. The DN400 branch is GRE at the DN800 x DN400 tee and continues in steel. Stresses in the steel were not assessed; the steel was included for its effect on the DN800 GRE line. The DN80 branch was modelled without continuation, as the received continuation drawing shows the line ending after the DN80 valve. The bellow was modelled with typical stiffness values for a rubber single-arch expansion joint.
The caisson connection was modelled as an anchor because the caisson is much stiffer than the piping. The 3-way stop on the DN800 steel line was also modelled as an anchor; its presence follows from a received sketch. The two supports on the GRE line, a rest + guide (+Y and X) and a rest (+Y), were positioned according to a received drawing. The sketch showed a support under the tee, and the isometrics showed no pipe support. These discrepancies were recorded, and the support positions were based on the drawing.
Eight load cases were defined: four operating, two sustained and two expansion. They combine the weight of the pipe and its water content, the 10 barg design pressure, and design temperatures of 25°C and 5°C, 10°C above and below the 15°C installation temperature. The two expansion cases are the hot and cold pressurised operating cases minus the pressurised sustained case. In agreement with the client, no hydrotest condition was analysed; the integral spool had been hydrotested directly after production at the manufacturer’s site.
Bellow and Support Modifications and the Pressure Thrust Path
The analysis led to four required modifications with respect to the received isometrics and drawings, all marked up on the isometrics.
First, the bellow is moved from near the caisson to a GRE flange pair, to reduce the stresses in the GRE DN400 branch to an acceptable level.
Second, the bellow must be installed compressed by 12 mm. With this pre-compression, the maximum net extension of the bellow due to pressure is 16.4 mm minus 12 mm, or 4.4 mm. The pre-compression can be achieved with the same overall dimensions by replacing the four gaskets with a different type that is 3 mm thicker, which gives a total of 12 mm of extra installed spool length.
Third and fourth, two supports are added relative to the received isometrics, which showed no pipe support. The first is a rest + guide (+Y and X) between the DN400 branch and the new bellow position. The second is a rest (+Y) between the new bellow position and the DN80 branch.
The analysis also identifies the 3-way stop on the DN800 steel line as important. Because the untied bellow prevents the GRE line from accommodating the pressure thrust, the thrust must be accommodated by the 3-way stop.

Bellow Movements, GRE Stresses, Flange and Restraint Loads
With the bellow installed compressed by 12 mm, the modelled axial extension fell from 18.7 mm to 6.7 mm, within the 10 mm maximum allowed. Axial compression was 14 mm against 35 mm allowed, compared with 2 mm when installed in the normal way. Lateral movement was 1.3 mm against 16 mm in both cases. Angular movement was below 0.1 degree; no allowable is specified for it.
| Bellow movement | Installed normally | Installed 12 mm compressed | Maximum allowed |
|---|---|---|---|
| Axial extension | 18.7 mm | 6.7 mm | 10 mm |
| Axial compression | 2 mm | 14 mm | 35 mm |
| Lateral movement | 1.3 mm | 1.3 mm | 16 mm |
| Angular movement | <0.1 deg | <0.1 deg | Not specified |
Modelled axial extension, axial compression and lateral movement of the bellow, installed normally and with 12 mm pre-compression, against the maximum allowed values.
The GRE pipe stresses were within the ISO 14692 allowable values, and all GRE flange loads were within their allowable values. The flange check in CAESAR II converts the external axial force and bending moment on each flange into an equivalent internal pressure. In this conversion, the gasket-sealing circle is conservatively set equal to the outer diameter, and the axial force is taken as zero when compressive. This equivalent pressure is combined with the line pressure and assessed against an allowable equal to twice the line pressure rating, per the manufacturer’s specification. A safety factor of 0.67, 0.83 and 0.89 is applied for sustained, operating and occasional or hydrostatic load cases respectively.
The restraint summary reports the loads for which the support design is to be verified. The axial load at the caisson nozzle is approximately 140 kN. The axial load on the 3-way stop is approximately 650 kN, on the assumption that no bellow or other component in the steel DN800 continuation accommodates the pressure thrust. With the four modifications made, the requirements for stress and maximum allowed bellow displacements are fulfilled.
Poisson Contraction and Pressure Thrust at an Untied Bellow
With the untied bellow, there is no pressure-related axial stress in the GRE pipe. The same arrangement produced two effects that the analysis quantified. The first was approximately 16.4 mm of Poisson contraction at 10 barg, taken up as bellow extension against a 10 mm allowable. The second was approximately 650 kN of axial load on the 3-way stop on the DN800 steel line, on the assumption stated above.
The spool had already been produced, and all four modifications concern the bellow position, the bellow’s installed length and the supports on the GRE line. The pressure thrust is accommodated outside the GRE scope, by the 3-way stop on the DN800 steel line.
Frequently Asked Questions
Why does an untied bellow extend when a GRE line is pressurised?
With an untied bellow, internal pressure causes no axial stress in the GRE spool, but it does cause a positive hoop strain. Through the Poisson effect, this produces an axial contraction of the GRE pipe and an axial extension of the bellow. On this DN800 spool, the total axial contraction at the 10 barg design pressure was approximately 16.4 mm. With the bellow installed in the normal way, the modelled bellow extension was 18.7 mm against a 10 mm allowable.
Where is the pressure thrust taken when a bellow has no tie-rods?
The untied bellow prevents the GRE line from accommodating the pressure thrust, so the thrust must be accommodated by the 3-way stop on the DN800 steel line. In this analysis, the axial load on the 3-way stop was approximately 650 kN. This assumes that no bellow or other component in the steel DN800 continuation accommodates the pressure thrust.
How can a bellow be pre-compressed on a GRE spool that has already been produced?
The bellow is installed compressed by 12 mm. This can be achieved with the same overall dimensions by replacing the four gaskets with a different type that is 3 mm thicker, which gives a total of 12 mm of extra installed spool length. With this pre-compression, the maximum net extension of the bellow due to pressure is 4.4 mm. The modelled axial extension fell from 18.7 mm to 6.7 mm, within the 10 mm maximum allowed.
How are loads on GRE flanges checked in CAESAR II?
The flange check converts the external axial force and bending moment on each flange into an equivalent internal pressure. The gasket-sealing circle is conservatively set equal to the outer diameter, and the axial force is taken as zero when compressive. The equivalent pressure is combined with the line pressure and assessed against an allowable equal to twice the line pressure rating, per the manufacturer’s specification. A safety factor of 0.67, 0.83 and 0.89 is applied for sustained, operating and occasional or hydrostatic load cases respectively.
Which strength values define the ISO 14692 allowable stress envelope in this analysis?
The allowable stress envelope was drawn up from four GRE strength values: short-term biaxial hoop strength 250 MPa, short-term uniaxial strength 65 MPa, qualified strength 125 MPa and long-term uniaxial strength 32.5 MPa.