Deluge Piping Configurations and Upset Scenarios
Deluge fire water systems had been installed on three offshore monopiles. A surge (waterhammer) analysis was carried out for two purposes. The first was to determine the maximum pressure in each system and the unbalanced forces to be accommodated by the support system. The second was to recommend minimum deluge valve opening times and opening curves.
The piping was seamless steel with a design pressure of 19.7 barg and a test pressure of 29.6 barg. Water was supplied by a firewater pump on a barge, assumed to be approximately 20 m from the platform, through a flexible water hose. In each model, the hose was connected to one of two connection points at the top corners of the highest ring, and the other connection was kept closed. The pump was assumed to run for a short period against the closed deluge valve on the barge before the valve was opened.
Two upset scenarios were analysed. The first was slug loading on valve opening. When the deluge valve opened with the pump already running, water rushed into the empty piping. The momentum change as the water front hit each bend or tee generated an unbalanced reaction force. The second was a pump trip while the system was in operation. The trip was assumed to be caused by a mechanical failure, so the pump stopped almost instantaneously. The stop would send a pressure wave through the system that might lead to high pressures.
Two of the three monopiles are very similar, so only two systems, A and B, were analysed, in three configurations. Configuration A was a two-ring system with four sprinkler lines connected to the lower ring. Configuration A1 was a possible future variant of A, with four additional sprinkler lines connected to the upper ring, eight in total. Configuration B was a single-ring system with two sprinkler lines. The first few bends of configurations A and B are similar, so the valve-opening analysis used one model representing both. The pump trip was analysed separately for all three configurations.
BOSfluids Surge Model and Input Data
The analyses were performed in BOSfluids. The layout of each system was first modelled in CAESAR II from the supplied documents. It was then imported into BOSfluids, where surge elements such as the pump and the deluge valve were added.
Pump data was limited. A pump curve was assumed, with the working point set at 11.6 barg, the highest pressure in the available data. This corresponds to a flow rate of 350 m³/hr. The pump moment of inertia was set at 1 kgm², taken small to represent an instant pump trip. The pump suction pressure was set at 0.1 barg.
The flexible water hose between the pump and the platform was simulated with a wave speed of 300 m/s, against approximately 1,300 m/s in the steel pipe. The fluid was modelled as seawater at 20°C with a density of 1,000 kg/m³ and a bulk modulus of 2.2 × 10⁹ N/m².

Slug Loads on Deluge Valve Opening
When the deluge valve opens, the water front runs like a slug through the approximately 20 m flexible hose towards the first bend. The total unbalanced force at the bend has two contributions:
- Slug force. This is the simulated force from the slug entering the bend. The water front decelerates and experiences an additional pressure drop, and the corresponding pressure wave runs upstream.
- Momentum force. This is calculated from the slug velocity, density and volume flux. It arises from the change in direction of the momentum flux in the bend while the pipe downstream is still empty.
The momentum force is the main contribution and is proportional to the slug velocity squared.
Instant opening of the valve was the most conservative case. The slug reached a maximum velocity of 15.77 m/s towards the first bend. The total unbalanced force at bend 1 was 2.6 kN, made up of a slug force of 350 N and a momentum force of 2,287 N. The total fell to 2.3 kN at bend 2 and 2.1 kN at bend 3. Friction built up during filling gradually reduces the slug velocity and thereby the unbalanced forces.
The slug velocity was then determined for valve openings in steps of 5%. It was 6.8 m/s at 5%, 10.9 m/s at 10%, 12.9 m/s at 15% and 13.9 m/s at 20%. The analysis concluded that a significant reduction in slug velocity was only possible at small valve openings.
At 6.8 m/s, the slug needs about 3 seconds to cover the approximately 20 m from the deluge valve to the first bend. If the valve opens continuously and is 5% open after 3 seconds, the total opening time is 60 seconds. With this opening time, and with the slug arriving at the first bend at 6.8 m/s, the momentum force there fell to 425 N. The total unbalanced forces at the first three bends were 484 N, 445 N and 431 N, approximately 500 N. A 60-second opening time was considered long for a fire water system.
The recommendation was to open the valve in two stages: to 5% of its stroke in the first 4 seconds, then to 100% in the following 4 seconds.
Firewater Pump Trip Pressures and Unbalanced Forces
The maximum pressures were 10.7 barg for configuration A, 10.8 barg for A1 and 10.9 barg for B. All were well below the occasional allowable pressure of the system, taken as the test pressure of 29.6 barg.
The maximum unbalanced forces were 3.7 kN for configurations A and A1 and 3.9 kN for B. The 3.9 kN exceeded the 2.6 kN found for instant opening of the deluge valve, so the pump trip case determines the loads on the platform support system. The highest unbalanced forces arose in the longer steel sections of the piping; in configuration B these were the long starting and ending steel sections. The unbalanced forces in the flexible hose were moderate.
| Configuration | Rings | Sprinkler lines | Maximum pressure (barg) | Maximum unbalanced force (kN) |
|---|---|---|---|---|
| A | 2 | 4 | 10.7 | 3.7 |
| A1 | 2 | 8 | 10.8 | 3.7 |
| B | 1 | 2 | 10.9 | 3.9 |

Deluge Valve Stroke and Flexible Hose Modelling
Two points from the analysis apply to the design of these deluge systems.
The first concerns the deluge valve stroke. The momentum force at a bend is proportional to the slug velocity squared. The analysis identified the slug velocity at the start of the opening process as the important feature, which is the basis of the two-stage recommendation. No valve data was available, so the recommended two-stage opening rests on an assumed line-size gate valve with a linear relation between stroke and capacity.
The second concerns the flexible hose. The hose between the pump and the platform was simulated with its own wave speed, lower than that of the steel pipe. In a pump trip, the lower pressure wave velocity through the hose results in lower pressures and unbalanced forces.

Frequently Asked Questions
What unbalanced force does a slug create at the first bend when a deluge valve opens instantly?
In this analysis the total was 2.6 kN at bend 1: a 350 N slug force and a 2,287 N momentum force. The slug arrived at 15.77 m/s after approximately 20 m of flexible hose. The total fell to 2.3 kN at bend 2 and 2.1 kN at bend 3.
Which component makes up most of the unbalanced force at a bend during deluge valve opening?
The momentum force does. It comes from the change in direction of the momentum flux while the pipe downstream of the bend is still empty. It is proportional to the slug velocity squared and made up 2,287 N of the 2.6 kN total at the first bend.
How should a deluge valve open to reduce slug loads?
Slowly at the start of the stroke, because a significant reduction in slug velocity was only possible at small valve openings: 6.8 m/s at 5%, against 15.77 m/s for instant opening. A continuous 60-second opening reduced the total unbalanced forces at the first three bends to approximately 500 N, but this was considered long for a fire water system. The recommendation was a two-stage opening: to 5% of stroke in 4 seconds, then to 100% in the next 4 seconds. This is based on an assumed line-size gate valve with a linear relation between stroke and capacity.
Is a pump trip or deluge valve opening the design case for deluge piping supports?
Here it was the pump trip. Its maximum unbalanced force of 3.9 kN, in the single-ring configuration, exceeded the 2.6 kN at the first bend for instant valve opening. The pump trip case therefore determines the loads on the platform support system.
What pressures does a firewater pump trip produce in deluge piping?
Across the three configurations, maximum pressures reached 10.7, 10.8 and 10.9 barg. All were well below the occasional allowable pressure of 29.6 barg, taken as the test pressure.
How does a flexible hose between the pump and the platform affect pump trip surge?
The hose was simulated with a wave speed of 300 m/s, against approximately 1,300 m/s in the steel pipe. The lower pressure wave velocity through the hose results in lower pressures and unbalanced forces. In the pump trip results, the forces in the hose were moderate, and the highest forces arose in the longer steel sections.