News & Insights from Dynaflow Research Group

Software

Upcoming webinar

Analysis of Surge problems with CAESAR II and BOSfluids 5.4 The webinar Together with Hexagon PPM, DRG is co-hosting a free webinar on Analysis of

Read More »
alba_b3_news
Fluid Flow

Alba B3 platform installed

Alba B3 platform installed – DRG performed surge analysis It is always nice to see your computer models becoming reality! DRG performed a surge analysis

Read More »
Fluid Flow

Hades used in PhD Huan He

Titel: Computational Modelling of Particle Packing in Concrete By Huan He Physical particle packing is becoming a hot topic in concrete technology as more and

Read More »
Dynaflow Research Group

Hades used with Porosity of Concrete

Titel: Porosity of Concrete – Morphological Study of Model Concrete By Jing Hu Porosity of Concrete has developed a comprehensive methodological framework for characterizing geometrical

Read More »
Fluid Flow

Hades used in PhD Jianjun Zheng

Titel: Mesostructure of concrete Stereological analysis and some mechanical implications By Jianjun Zheng On the mesoscale, concrete can be considered as a composite material consisting

Read More »
Uncategorized

Pulsations Paper

Benefit of computational simulation of a pulsation dampener compared to an analytical method Accumulators are used to reduce pressure pulsations from reciprocating pumps by adding

Read More »
Streamlines through the bend and silencer from the CFD model, coloured by velocity magnitude (scale 0 to 60 m/s). A turbulent region is visible in the lower part of the silencer inlet.

CFD Root Cause Analysis of a Recirculation Silencer Failure

A Commissioning Failure That Sent Debris Downstream During commissioning of a natural gas compressor station, pieces of fibreglass fabric, mineral wool and steel wire were found throughout the downstream system. A small amount of mineral wool was also found in the surge valve. Inspection showed that the mineral wool found

Learn More »
Maximum operating temperature in the cooler system model: 85°C (purple) and 45°C (pink).

Static Stress Analysis for Gas Air Cooler Systems

The station model of the Winksele Compressor Station, to be built in Belgium, was divided into two models with some mutual overlap, a compressor model and a filter model, each covered by a separate stress report. A third report covers the gas air coolers as model C, an add-on to

Learn More »
CAESAR II model plot of a GRE pipe run coloured by wall thickness in mm. The pipe shown is the 2.4 mm section.

Static Stress Analysis of an Underground GRE Firewater System

Seventeen underground GRE firewater subsystems at a degassing station were analysed in CAESAR II for three load cases, hydrotest, operational and sustained, to ISO 14692. It may be concluded that, upon implementation of the recommendations, the static pipe stresses are acceptable and the flange loads are moderate. Underground GRE Firewater

Learn More »
CAESAR II model plot of one buried GRE subsystem showing applied wall thickness by colour.

Static Stress Analysis of a Buried GRE Firewater System Upgrade

Thirteen buried GRE firewater subsystems were modelled in CAESAR II and assessed to ISO 14692 for hydrotest, operating and sustained load cases. On implementation of the recommendations, static pipe stresses are acceptable and flange loads are moderate. The buried glass-reinforced epoxy (GRE) piping in the firewater system upgrade at a

Learn More »
Model view of the re-routed pumping station loops and platform piping, with supports shown as arrows.

GRE Firewater Line on a Jetty with Moving Trestles

The main firewater line for a new oil terminal jetty is made from glass reinforced epoxy (GRE) pipe. It starts at the onshore transition between underground and above-ground pipe, where it connects to steel lines, and follows a jetty about 1.5 km long. A firefighting platform about one third of

Learn More »
Static analysis model of one buried GRE system. New piping is shown in pink and existing piping, included as continuation piping, in purple.

Stress Analysis of an Underground GRE Firewater Extension

Nine underground GRE firewater systems, 77 stressed isometrics in total, were analysed in CAESAR II against the ISO 14692 allowable stress envelopes, with soil-pipe interaction modelled to the American Lifelines Alliance (2001) soil model. Modifications included a support bracing, polystyrene foam, NBR gasket stiffness limits and additional laminate for a

Learn More »
The report concludes that the results for the transient cases stay within the allowable figures for the applicable piping if valve closure rates are limited and simultaneous hydrant closures are avoided. It recommends that the closure of the open hydrants be distributed over a time interval and that the interval between closures be prevented from dropping below 0.5 seconds. As an alternative, the closure time of each hydrant could be stretched beyond 1 second per inch of line size. Both closure analyses used the same rate of 1 second per inch for each hydrant. Simultaneous closure over 3 seconds exceeded the allowable. Closure at 0.5 second intervals over 8.5 seconds gave 20.3 barg. Both peaks were assessed against the 26.6 barg occasional-load allowable.

Firewater Ring Main Extension in Buried GRP Piping

A new unit was added to an existing gas complex, and the firewater ring main was extended to serve it. Three sets of four 3-inch hydrant valves were modelled, twelve hydrants in total. Each hydrant is required to produce a minimum of 1452 l/min at 7.0 barg, and the hydrant

Learn More »